Hiper 60 DHW/15 HTG HIU

Hiper 60 DHW/15 HTG HIU
image for Hiper 60 DHW/15 HTG HIU
alternative image for Hiper 60 DHW/15 HTG HIU
alternative image for Hiper 60 DHW/15 HTG HIU
£1,360.00
Hiper60/15 : £1,360.00
In Stock
  • Description
  • Specification
  • Delivery

Hiper Xi60L INDIRECT HIU 60DHW/15HTG

Communal Heat Networks

A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

Each home or apartment has its own HIU (heat interface unit), which converts heat from the network as heating and hot water for the home.

 

 

Advantages for Designers, Developers and Architects

  • Gas supply not required for an HIU
  • No flues to evacuate exhaust combustion
  • No storage cylinder required
  • Meets low emission and efficiency targets

Advantages for the installers

  • Easy to install, add only a programmable room thermostat
  • Compact and lightweight
  • Minimal installation requirements for pipe work.
  • Simple maintenance and easy access to all components

Advantages for Landlords

  • Reduced service and maintenance costs
  • Metered energy usage for fairer tenant billing
  • Practical for combining with lower cost renewable technologies
  • No flues to maintain for health and safety laws

Advantages for the Tenant

  • Shared maintenance costs
  • Efficiently controlled heating and hot water supply
  • Accurate billing for only the actual energy used
  • Awareness of energy consumption promotes energy saving

The Hiper HIU FEATURES

 

                    

Pressure Independent Control integral PICV with electric actuator giving propor-

tional modulating control as instructed by the PID Controller, 100% authority, (regardless of pressure fluctuations in the district heating supply). Unlike many other HIU, no further control valves (for example DPCV) are required.

 

                     

Automatic Fault Diagnostics The control unit can identify faults to components within the HIU and issues an identifying fault code on the screen. Once the fault or error has been rectified the the control unit automatically resets and resumes normal operation.

 

                    

Instant Hot Water Response - Instant water response is guaranteed by keeping heat (supplied by the district supply) close at hand to the HIU at all times. At regular intervals (factory set to 20 minutes), the controller opens (factory set to 2 min) the PICV to deliver a low flow of about 100 l/hr, then closes the valve again. This repeats whenever the HIU is on standby when there is no demand.

                    

DHWS Priority - DHWS is the priority operation of the HIU. A flow switch detects the demand and the HIU (if in heating mode) switches to DHW production. Even if the heating system is in fault mode, the HIU will still produce DHWS.

 

                    

Proven reliable components. Low energy Erp compliant pump. Unique inlet Block with By Pass, test points, meter sensor port and uniquely design strainer with increase sur- face area for longer duty without blocking or reduced performance over a standard pattern Y Strainer.

 

 

The Hiper HIU FEATURES

 

                     

Underfloor Heating - the unit is fully compatible with low temperature systems. The installer simply sets the required value for temperature on installation.

Full detail available in the installation manual.

 

                     

Prepayment Billing can be accommodated with an accessory kit to shut down the unit when the tenant is no longer in credit.

 

 

                     

HIU Hibernation mode - press the start button and hold for 3 seconds and the HIU will shut-down. The PICV valve will shut, and heating, hot water and standby functions will be disabled. Press the start button to resume normal operation. This is a function for when the apartment is unoccupied or for the  tenant during holiday periods.

 

 

PROVEN PERFORMANCE.

The HIPER HIU has been independently tested and proved conforms to BS EN132-01

 

BS EN132-01is the British Standard for;

‘Gas fired domestic appliances producing hot water – Appliances not exceeding 70 kW heat input and 300 lt water storage capacity – Part 1, assessment of performance of hot water deliveries”,

 

The HIU was tested, awarded 2 Stars, and measured on delivery of DHW at 55C, with a DH flow temp of 70C.

 

 

 